NIZHNY NOVGOROD: +7 (831) 214-19-88
MOSCOW: +7(495) 663-71-70
As part of centralized installations, they can simultaneously protect a large number of premise. Available in sprinkler and deluge configurations.
The aggregate water mist fire extinguishing installation comprises the following main components:
- High pressure pump station with electric pumps (primary and backup);
- Tank with specially prepared water of various capacities, in accordance with the required volume;
- Stainless steel switchgear with manual and electric drive for supplying water to nozzles in various zones;
- Special sprinkler or deluge sprayers (quantity is determined by calculation);
- Pipelines and special connecting devices made of stainless steel.
Коллектор напорный
Pressure collector
Шкаф аппаратуры коммутации
Switchingcabinet
Резервный насос высокого давления
High pressure standby pump
Рабочий насос высокого давления
High pressure working pump
Коллектор питающий
Supply manifold
Жокей-насос
Jockey pump
Бак мембранный
Membrane tank
От водопровода
From the water supply line
Бак противопожарного запаса воды
Fire water tank
Насос повышения давления на всасывающей линии
Suction line pressure increase pump
Basic specifications of the installation
Sl. No.
Parameter
Value
1
Climatic configuration
У3 as per GOST 15150-69
2
Degree of protection with enclosures against ambient exposure
At least IP54 as per GOST 14254-80
3
Working pressure, bar
120
100
80
4
Maximum tolerable pressure, bar
130
5
Pump supply, L/min.
48
150
200
6
Inlet water pressure, bar
7
Electric engine power, kW
10.9
18.8
22.8
30.1
8
Installation power supply
1 or 2 power points: 3-380 V±10%, 50±1Hz
9
Overall dimensions of the installation
width-600, height-1100, depth-650
10
Weight of the installation, kg
11
Maximum ambient temperature, °С
55
Certificates
Design manual
Catalogue